● Featured Guides
Explore 21 CNC learning topicsLearn condition monitoring from real dataUse the free CNC calculators

3-Phase Power & Motor Sizing Calculator

Calculate required amperage, wire size (AWG), and breaker size for 3-phase industrial motors. Includes voltage drop check for long cable runs. Based on NEC Article 430.

Free Tool · NEC Art. 430 · Wire & Breaker Sizing · Voltage Drop
Motor Parameters
V

460 V is the most common US industrial voltage. 480 V is the nominal utility supply; motors are rated 460 V to allow for line losses.

60%75%85%95%+

Typical 3-phase induction motors: 80–90% at full load.

70%80%91%98%

NEMA Premium motors: 91–96%. Standard efficiency: 85–91%.

Circuit Protection & Voltage Drop
🔌

NEC 430.52: Inverse-time breakers up to 250% FLC to handle starting inrush.

SF
📏 ft

Distance from panel to motor. NEC recommends ≤3% voltage drop on branch circuits.

Results
NEC FLC (Table 430.250)
use for conductor sizing
Calculated FLA
formula-based (reference only)
Min. Wire Size (AWG)
NEC 430.22 · 125% FLC
Max. Breaker Size
NEC 430.52 max
Overload Relay Setting
NEC 430.32
Starting Inrush (~6× FLA)
DOL starting estimate
Voltage Drop
Detailed Summary
Amperage
NEC FLC (Table 430.250)
Calculated FLA
Conductor sizing (125% FLC)
Starting inrush (~6×)
Circuit Protection (NEC Art. 430)
Max. breaker (430.52)
Overload relay max (430.32)
Min. disconnect (430.102)
Conductors
Min. wire size
Wire ampacity
Voltage Drop
Calculated voltage drop
Voltage drop %
NEC recommendation
Inputs Used
Motor power
Voltage
Power factor / efficiency
Cable / conductor

How 3-Phase Motor Sizing Works

Sizing a 3-phase motor circuit requires four steps per NEC Article 430: calculate full-load current (FLC), size conductors at 125% FLC, size the breaker, and set the overload relay. Use NEC Table 430.250 FLC for conductors and breakers, and nameplate FLA for the overload relay only.

1 Full-Load Current

The formula calculates FLA from kW, voltage, efficiency, and power factor. For conductor and breaker sizing, always use NEC Table 430.250 — values are intentionally conservative.

FLA (3φ) = (kW × 1000) ÷ (√3 × V × PF × η) √3 = 1.732

2 Wire Sizing (430.22)

Branch circuit conductors must be sized at minimum 125% of NEC FLC. For 10 HP / 460V: 14 A × 1.25 = 17.5 A → #12 AWG copper (20 A rated).

Min. Ampacity = NEC FLC × 1.25 Select AWG from NEC Table 310.16 (75°C Cu column)

3 Breaker Sizing (430.52)

Breakers are oversized to handle starting inrush (5–8× FLC). NEC 430.52 allows inverse-time breakers up to 250% of NEC FLC. Next standard size up is permitted.

Max Breaker (ITCB) = NEC FLC × 250% Standard sizes (240.6): 15,20,25,30,35,40, 45,50,60,70,80,90, 100,125,150,175,200A

4 Overload & VDrop

Overload (NEC 430.32) uses nameplate FLA — 125% for SF≥1.15, 115% for SF=1.0. Voltage drop check: ≤3% on branch circuit recommended.

OL Relay (SF≥1.15): Nameplate FLA × 125% VD (3φ) = √3 × I × R × L/1000
NEC Table vs. Nameplate

Use NEC Table 430.250 FLC for conductors (430.22) and breakers (430.52). Use motor nameplate FLA for overload relay (430.32). Never cross-use these values. Always have a licensed electrician verify all motor circuit designs before installation.

Example Calculations — 3 Real-World Scenarios

These worked examples show the calculator in action across three common U.S. industrial situations. All use 460V, 3-phase, copper conductors, inverse-time breaker (250% FLC), and NEMA SF 1.15.

🔵 CNC Milling Machine
Scenario — 10 HP VMC, 100 ft run
Motor: 10 HP / 460V 3-phase PF / Eff: 85% / 91% Cable: 100 ft copper Breaker: ITCB (250%)
NEC FLC: 14 A · Wire: #12 AWG
Breaker: 35 A · VDrop: ~0.8%
100 ft is well within the ≤3% limit. #12 AWG copper at 20 A ampacity meets the 17.5 A minimum (14 A × 1.25). Overload relay set at ≤17.5 A (nameplate FLA × 125%).
🟠 Batch Plant Mixer Motor
Scenario — 50 HP, 350 ft long run
Motor: 50 HP / 460V 3-phase PF / Eff: 85% / 93% Cable: 350 ft copper Breaker: ITCB (250%)
NEC FLC: 65 A · Wire: #4 AWG
Breaker: 175 A · VDrop: ~2.9%
At 350 ft the voltage drop is at the NEC 3% limit — marginal. For critical production motors, upsize to #3 AWG to bring drop below 2.5%. Starting inrush ~390 A — confirm bus capacity.
🔴 Press Brake Hydraulic Pump
Scenario — 25 HP, 250 ft run, Al wire
Motor: 25 HP / 460V 3-phase PF / Eff: 80% / 90% Cable: 250 ft aluminum Breaker: ITCB (250%)
NEC FLC: 34 A · Wire: #2 AWG Al
Breaker: 90 A · VDrop: ~2.4%
Aluminum wire requires 2 AWG sizes larger than copper for equivalent capacity. At 250 ft VDrop stays below 3%. Use AL/CU rated terminations only — aluminum wiring at copper-only terminals is a fire hazard.

NEC Table 430.250 — 3-Phase AC Motor Full-Load Currents

Full-load currents from NEC Table 430.250 for induction-type squirrel cage motors. Required for conductor and overcurrent device sizing per NEC 430.6(A)(1).

HP208 V230 V460 V575 VMin. Wire (Cu)Max. Breaker
1/22.42.21.10.9#14 AWG15 A
14.64.22.11.7#14 AWG15 A
27.56.83.42.7#14 AWG15 A
516.715.27.66.1#14 AWG20 A
10Common30.828.014.011.0#12 AWG35 A
2574.868.034.027.0#8 AWG90 A
50Heavy14313065.052.0#4 AWG175 A
100Large27324812499.0#1 AWG300 A
2005284802401924/0 AWG600 A
10 HP
460V FLC14 A
Min. Wire#12 AWG
Max. Breaker35 A
25 HP
460V FLC34 A
Min. Wire#8 AWG
Max. Breaker90 A
50 HP
460V FLC65 A
Min. Wire#4 AWG
Max. Breaker175 A

AWG Copper Wire Ampacity — 75°C (NEC Table 310.16)

#14
15 A
≤ 2 HP / 460V
#12
20 A
≤ 10 HP / 460V
#10
30 A
≤ 20 HP / 460V
#8
50 A
≤ 30 HP / 460V
#6
65 A
≤ 40 HP / 460V
#4
85 A
≤ 50 HP / 460V
#3
100 A
≤ 75 HP / 460V
#2
115 A
Medium load
#1
130 A
≤ 100 HP / 460V
2/0
175 A
Medium-large
3/0
200 A
≤ 150 HP / 460V
4/0
230 A
≤ 200 HP / 460V

Frequently Asked Questions

NEC 430.52 permits inverse-time breakers up to 250% of NEC FLC to handle motor startup inrush (5–8× FLC). The wire is protected by the overload relay (continuous overcurrent) and the breaker handles true short circuits. Wire ampacity must still be ≥125% FLC per NEC 430.22.
FLC = NEC Table 430.250 values — use for conductor sizing (430.22) and breaker sizing (430.52). FLA = motor nameplate — use for overload relay (430.32) only. Never cross-use these values.
480V is the nominal utility supply. Motors are rated 460V to account for voltage drop in distribution. Always use the 460V column of NEC Table 430.250 for 480V systems.

Related Industrial Tools

Estimates for planning only. Always size per NEC Article 430 and local codes. Always have a licensed electrician perform final design and installation. © TWC Industrial

Motor Sizing Calculator · Free to Use

Top Picks for CNC Router Tooling

Professional-grade carbide tools ready to ship. Click any product to view details and pricing.

15-Piece Router Bit Set

15-Piece Router Bit Set

Multi-size starter kit with carrying case

View on Alibaba →
Compression Spiral Router Bits

Compression Spiral Bits

Clean edges on plywood & MDF

View on Alibaba →
ER Collet Set

ER Collet Set

Precision holding, zero runout

View on Alibaba →

As an Alibaba affiliate partner, we earn from qualifying purchases at no cost to you.